MS 110/10(6) kV

Modular substations for a rated voltage of 110 kV are intended for receiving, converting and distributing electrical energy of an alternating three-phase current with a frequency of 50 Hz.
E-houses are used at electric grid facilities, in power supply systems of industrial enterprises, gas and oil-producing industries, at rural and urban facilities, and also in railway transport.

     MS distinguishing features

  • MS is a product of maximum operational readiness.
  • Ability to install various types and composition of equipment in accordance with the Customer’s requirements.
  • Possibility of increasing connections on a modular basis.
  • Convenience of assembling and operation.
  • Mobility and easiness of transportation of container storage units by road and rail.
  • Reducing the duration of commissioning works by reducing the scope of work required to install equipment at the facility.
  • Reducing the size of the land parcel and the construction works scope on the site arrangement for the substation installation by reducing the substation dimensions in a mobile modular version.
  • Ability of connection to cable as well as to overhead power lines.

MS operation conditions

  • MS climatic version and placement category — Y1, XL1 by GOST 15150-69;
  • ambient air temperature from -60° C to +40° C;
  • type II atmosphere – industrial, environment – non-explosive, free of dust in concentrations that reduce the product parameter
  • air relative humidity up to 80% at the temperature of 20ºС;
  • installation altitude above sea level is no more than 1000 m;
  • wind speed up to 36 m/s (wind pressure up to 80 daN) in the absence of atmospheric ice, wind speed up to 15 m/s (wind pressure up to 14 daN) with the atmospheric ice with its thickness of 20 mm;
  • seismic resistance is 8 points per MSK- 64.

MS of 110 kV composition includes:

  • gas insulated switchgear 110 kV;
  • power oil transformer 110 kV;
  • cubicle switchboard 35 (20, 10, 6) kV;
  • auxiliary power transformer;
  • the operational power system with a compact storage battery and a recharging device;
  • relay protection and automatic equipment cabinet;
  • central alarms cabinet;
  • alternative current in-house cabinet;
  • telemetry equipment cabinet;
  • metering cabinet;
  • container storage unit;
  • jumper cables.

The configuration and composition of the equipment used in E-houses can be changed at the Customer’s request in accordance with the technical specification requirements.

Technical parameters and characteristics

Parameter name Parameter value
Rated voltage, kV
— high 110
— medium 35, 20
— low 35, 20, 10, 6
Supply transformer capacity, MVA Up to 80
Frequency of alternative electric current, Hz
Rated current of bus bars, А 630, 800, 1000, 1250, 1600, 2000, 2500, 3150
Rated voltage of auxiliary circuits, V
DC 220
AC 220, 380
Switchgear 110 kV parameters:
– rated thermal current(1 s), кА Up to 50
– electrodynamic withstand nominal current, кА Up to 128
– cutoff current of the fault interrupter switch, кА Up to 50